MAXI-INT4-I

4-20mA or 0-10V input integrated with respect to time. Switch between total and the instantaneous rate.
Digit Height

20mm

Displayed Reading

Scalable

Excitation

24V DC @ 30mA

Analogue Output

-10 to +10V, 4-20mA, 0-10V

Alarm Outputs

4 x SPST mechanical relays (AL4), 2 x solid state relays (DSS), 4 x solid state relays (QSS), 2 x SPCO mechanical relays (SPCO)

Data Interface

RS232, Modbus RTU, RS422/RS485 + Modbus ASCII

Number of Digits

6

Digit Colour

Red (R), Green (G)

Supply Voltage

95-265V AC (AC), 11-30V DC (DC)

Power Burden

10VA maximum

Bezel Size

96mm wide x 48mm high

Panel Cutout

92mm wide x 45mm high

Depth Behind Panel

125mm

Front Panel Sealing

IP65 standard, IP67 with optional SPC4 cover

Operating Temperature

0C to +50 Deg. C

Option ANB

Output: -10 to +10V
Drive Capacity: >1k Ohms
Accuracy: +/-20mV
Resolution: 16 bit D/A, better than 0.2mV

User Manual

Option ANI

Output: 4-20mA
Drive Capacity: <500 Ohms
Accuracy: +/-10uA
Resolution: 16 bit D/A, better than 0.4uA

User Manual

Option ANV

Output: 0-10V
Drive Capacity: >1k Ohms
Accuracy: +/-10mV
Resolution: 16 bit D/A, better than 0.2mV

User Manual

Option AL2

Format: 2 x SPST mechanical relays
Contact Rating: 2A @ 250V AC

User Manual

Option 232

Output: RS232 ASCII

User Manual

Option 485

Output: RS422 / RS485 ASCII and Modbus ASCII

User Manual

Option RTU

Output: RS485 Modbus RTU

User Manual

Applications

A crane overload monitoring and alarm system using INT4 digital panel meters.

A crane overload monitoring and alarm system using INT4 digital panel meters.

A group of INT4 digital panel meters in a batching control panel.

An INT4-C counter mounted on a concrete batching vehicle.
As it is subjected to road spray from the wheels of the truck, it is protected by our IP67 cover. It also has daylight viewing LEDs so that it can be clearly read in sunlight.

A FUSION large digit display with 200mm high digits is summating the loads measured by 6 x INT4-L load cell panel meters.
Summation is digital with data collected over a 3-wire RS485 data link.

10 x INT4 digital panel meters DIN rail mounted inside a control cabinet for a filling line.