Output Options For Your Fusion Display
The Fusion range utilises a modular construction technique that enables you to configure it with the exact functionality you require, this flexible approach ensures that you only pay for the features you need. The output options are available for you to add to your display.- Analogue Output
- - 10 to + 10 V
- 4-20 mA
- 0-10 V
- Alarms
- 2 x SPST mechanical relays
- 4 x SPST mechanical relays
- 2 x solid state relays
- 4 x solid state relays
- 2 x SPCO mechanical relays
- 4 x SPCO mechanical relays
- Serial Output
- RS232
- RS422/RS485 + modbus ASCII
- Modbus RTU
Function
The Fusion range utilises a modular construction technique that enables you to configure it with the exact functionality you require, this flexible approach ensures that you only pay for the features you need. The output options are available for you to add to your display.
Option ANB
Output: -10 to +10V
Drive Capacity: >1k Ohms
Accuracy: +/-20mV
Resolution: 16 bit D/A, better than 0.2mV
Option ANI
Output: 4-20mA
Drive Capacity: <500 Ohms
Accuracy: +/-10uA
Resolution: 16 bit D/A, better than 0.4uA
Option ANV
Output: 0-10V
Drive Capacity: >1k Ohms
Accuracy: +/-10mV
Resolution: 16 bit D/A, better than 0.2mV
Option AL2
Format: 2 x SPST mechanical relays
Contact Rating: 2A @ 250V AC
Option AL4
Format: 4 x SPST mechanical relays
Contact Rating: 2A @ 250V AC
Option DSS
Format: 2 x solid state relays (specify AC or DC)
Contact Rating: 2A @ 250V AC
Option QSS
Format: 4 x solid state relays (specify AC or DC)
Contact Rating: 2A @ 250V AC
Option SPCO
Format: 2 x SPCO mechanical relays
Contact Rating: 2A @ 250V AC
Option 232
Output: RS232 ASCII
Option 485
Output: RS422 / RS485 ASCII and Modbus ASCII
Option RTU
Output: RS485 Modbus RTU
Option RTC