The meters and controllers on this page accept pulse inputs from such sensors as NPN, PNP or namur proximity switches, rotary encoders etc. All can be easily scaled to read in RPM, frequency, metres per minute etc..
Suited for these applications and more:-
The INT-F is a low cost yet highly flexible and easy to use 1/8 DIN scalable rate/frequency meter.
It can also be used as a counter/totaliser with 1 or 2 input channels.
It has a number of useful plug-in options which make it ideal for use in many control and monitoring applications.


|
| Input connections | One input channel used. Excitation voltage output. |
| Input Signal | The meter can accept NPN, PNP, contact closure, 5V pulse, 24V pulse, low level AC and high level AC signals. Debounce filtering for contact inputs.
Frequency range 0.03Hz to 50 000 Hz. |
| Excitation | 24V DC up to 100mA |
| Digits | 5 digits, 14mm high. Legible up to 7 metres away |
| Digit colour | Red or green |
| Scaling | Digital menu-free system. Floating point scale factors for precise scaling.
No need to calculate scale factors - simply enter a typical input frequency and desired reading value and the meter will compute scale factor automatically. |
| Filtering | Adjustable 0 to 5 Seconds |
| Last digit Round-up | Selectable 1,2,5,10,20,50 |
| User linearisation | not available on this model |
| Front panel controls | Calibration, Reset, Max/Min, Alarms |
| Power | 11-30VDC or 95-265 VAC |
| Accuracy | +/-0.01% of range |
| Thermal stability - range | +/- 100ppm/oC. Trimmed Quartz crystal internal reference. |
| Thermal stability - offset | no offset errors |
| Analogue output | Optional plug-in module 4-20mA into 0 to 500 Ohms 0-10V into loads>600 Ohms -5 to+5V into loads>600 Ohms Fully isolated from input and power Fully scalable with digital precision Forward and reversion action possible
|
| Alarm output | Optional plug-in modules 2 Alarms rated 5A 250VAC, SPST 4 Alarms rated 5A 250VAC, SPST Adjustable hysteresis Energise or de-energise on trip Normally open or closed |
| Serial data output | Optional plug-in modules. RS232 1200 baud output only. RS422 1200 baud output only. RS485 Addressable DeviceNet Addressable Modbus Addressable Profibus DP Addressable |
| Logic inputs | TARE, Peak/Valley and RESET |
| Connectors | Detachable screw terminals |
| Bezel size | 96mm wide x 48mm high. 13mm forward. |
| Panel cutout | 92mm wide x 45mm high. +1mm, -0mm |
| Depth behind panel | 125mm including connectors + cable. |
| Sealing | IP65 standard, IP67 with optional SPC4 cover |
| See operating Manual |
| See datasheet |